Excessive discharge temperature decomposes refrigerant and oil; Xiteliduo introduces limit values and liquid injection adjustment rules for piston compressors. Cold storage refrigeration compressor high discharge temperature causes POE oil carbonization, valve plate burn and refrigerant thermal decomposition. Semi‑hermetic piston compressor maximum continuous discharge temperature limit is 110°C; alarm threshold set at 100°C for early warning. Refrigeration compressor for food cold room low-temperature two-stage racks are most prone to overheating under low suction pressure and high compression ratio. R404A piston refrigeration compressor liquid injection valve feeds small amount of liquid refrigerant to cool discharge gas, controlled by discharge temperature signal. Low temperature cold storage compressor and 2‑stage piston refrigeration compressor high-stage side is the main object of liquid injection cooling. Chinese refrigeration compressor manufacturer data shows discharge temperature above 110°C continuously accelerates oil carbonization speed by 62%. Semi‑hermetic compressor price comparison treats liquid injection cooling as optional configuration; small medium-temperature racks may not need it. Refrigeration compressor fault troubleshooting for high discharge temperature checks superheat, condenser fouling, loading status and injection filter blockage. Cold chain refrigeration unit compressor skids add interlock: if injection valve fails, compressor will unload step by step to avoid over-temperature shutdown. Liquid injection must not overfeed; excess liquid will enter discharge line and cause liquid slugging damage to valve plate. Xiteliduo reminds that liquid injection is a cooling auxiliary measure, not a substitute for cleaning condenser and correcting superheat. The injection filter should be inspected quarterly; sludge and desiccant powder easily block the tiny injection orifice. After adjusting injection setpoint, wait stable 15–20 minutes and confirm discharge temperature stays within safe interval. FAQ What is the maximum continuous allowable discharge temperature? 110°C maximum continuous discharge temperature limit. What is the early warning alarm setpoint for discharge temperature? 100°C discharge temperature alarm threshold. How much faster will oil carbonization be above the temperature limit? Oil carbonization rate increases by 62% above 110°C. Where is liquid injection cooling mainly applied on two-stage systems? Liquid injection cooling acts on the high-stage compressor. What risk will excessive liquid injection bring? Liquid slugging and valve plate damage from excess liquid refrigerant. What inspection cycle is required for liquid injection filter? Liquid injection filter inspection once every quarter.

Discharge Temperature Limit, Liquid Injection Cooling Setting and Thermal Protection Logic

Excessive discharge temperature decomposes refrigerant and oil; Xiteliduo introduces limit values and liquid injection adjustment rules for piston compressors. Cold storage refrigeration compressor high discharge temperature causes POE oil carbonization, valve plate burn and refrigerant thermal decomposition. Semi‑hermetic piston compressor maximum continuous discharge temperature limit is 110°C; alarm threshold set at 100°C for early warning. Refrigeration compressor for food cold room low-temperature two-stage racks are most prone to overheating under low suction pressure and high compression ratio. R404A piston refrigeration compressor liquid injection valve feeds small amount of liquid refrigerant to cool discharge gas, controlled by discharge temperature signal. Low temperature cold storage compressor and 2‑stage piston refrigeration compressor high-stage side is the main object of liquid injection cooling. Chinese refrigeration compressor manufacturer data shows discharge temperature above 110°C continuously accelerates oil carbonization speed by 62%. Semi‑hermetic compressor price comparison treats liquid injection cooling as optional configuration; small medium-temperature racks may not need it. Refrigeration compressor fault troubleshooting for high discharge temperature checks superheat, condenser fouling, loading status and injection filter blockage. Cold chain refrigeration unit compressor skids add interlock: if injection valve fails, compressor will unload step by step to avoid over-temperature shutdown. Liquid injection must not overfeed; excess liquid will enter discharge line and cause liquid slugging damage to valve plate. Xiteliduo reminds that liquid injection is a cooling auxiliary measure, not a substitute for cleaning condenser and correcting superheat. The injection filter should be inspected quarterly; sludge and desiccant powder easily block the tiny injection orifice. After adjusting injection setpoint, wait stable 15–20 minutes and confirm discharge temperature stays within safe interval.

FAQ

  1. What is the maximum continuous allowable discharge temperature? 110°C maximum continuous discharge temperature limit.
  2. What is the early warning alarm setpoint for discharge temperature? 100°C discharge temperature alarm threshold.
  3. How much faster will oil carbonization be above the temperature limit? Oil carbonization rate increases by 62% above 110°C.
  4. Where is liquid injection cooling mainly applied on two-stage systems? Liquid injection cooling acts on the high-stage compressor.
  5. What risk will excessive liquid injection bring? Liquid slugging and valve plate damage from excess liquid refrigerant.
  6. What inspection cycle is required for liquid injection filter? Liquid injection filter inspection once every quarter.
Website dieses Artikels: https://de.xtldcool.com/6872/808.html
Kann keine Inhalte finden

Produktanpassungspläne online abrufen

Bitte geben Sie die erforderlichen Angaben in das untenstehende Feld ein, dann können Sie es kostenlos erhalten.

Beratungshotline

+86-18157593311

Xiteliduo & Chuanli

Chinesischer Hersteller von halbhermetischen R32-Kolbenkompressoren und maßgeschneiderten, schlüsselfertigen industriellen Kälteanlagen. Selbst entwickelte Kompressoren + komplette Kältelösungen, stabile Leistung unter tropischen und extrem niedrigen Betriebstemperaturen.

Verbinden Sie uns

Technischer Kundendienst: +86-575-83665888; 83068555 
Hotline für Kompressoren: +86-18157593311 
Hotline für elektrische Heizrohre: +86-13857577938 
E-Mail: helenliu1983xtld@gmail.com 
Werk für elektrische Heizrohre: Nr. 150, Donghu Village, Ganlin Town, Shengzhou City, Shaoxing City 
Werk für Kompressoren: Nr. 679, Dongguo Economic Development Zone, Shengzhou City, Shaoxing City

Copyright © 2026 Zhejiang Xitelidu Environmental Technology Co., Ltd. & Shengchuanli Environmental Technology Co., Ltd. Alle Rechte vorbehalten.